Purpose
To secure HVAC units mounted on vibration isolators.
Caution
When anchoring to post-tensioned slab, locate and avoid reinforcing.
Source: Noson, Perbix, SSD
Recommendation
Install restraint brackets or seismic snubbers.
Supplies Required
- Angle—6" x 6" x 1/2" x 4"
OR
- Bent plate—3/8"
- Lag bolts—5/8" diameter x 6" (for wood)
- Expansion bolts—5/8" diameter x 4" (for concrete)
- Flex-line
Source: Noson, Perbix, SSD
- Steel Z snubbers (or other seismic type snubber)
- 4 x blocking (for wood construction)
- Framing clips (for wood construction)
Installation
Source: Noson, Perbix, SSD
Restrain Bracket Installation
- Provide two angles or bent plates at each corner of the unit.
- Bolt to support with one bolt per angle. (For wood use two lag bolts at 3" spacing per angle.)
Seismic Snubber Installation
- Provide two snubbers at each corner of the unit.
- Bolt to support, providing sufficient free play to allow unit vibration under normal use.
Note
Provide Flex-line at piping (see Piping).